Model |
SLJ-3W SLJ-3 |
SLJ-4W SLJ-4 |
SLJ-6W SLJ-6 |
SLJ-11W SLJ-11 |
|
Temperature range |
-110~150℃ | ||||
Cooling capacity |
-120℃ | 3kw | 4kw | 6kw | 11kw |
-135℃ | 2.5kw | 3.3kw | 5kw | 9kw | |
Evaporator space | 2㎡ | 2.8㎡ | 4㎡ | 7.8㎡ | |
Evaporator | ᵠ16*40m | ᵠ22*40m | ᵠ28*45m | ᵠ28*45m*2 | |
Connection size | ᵠ16 ball mouth | ᵠ16 ball mouth | ᵠ16 ball mouth | ᵠ16 ball mouth | |
Compressor | DORIN | DORIN | DORIN | DORIN | |
Operation Panel | 7-inch color touch screen controller, temperature curve record, data export to excel format. | ||||
Control system |
Standard:single-ship microcomputer controller, Stepping control; Set temperature difference of refrigeration on&off.Optional:SIEMENS S7-200PLC&module |
||||
Condensor | KAORI Plate heat exchanger | ||||
Intermediate heat exchanger | KAORI Plate heat exchanger | ||||
Drying filter core | Danfoss | ||||
Expansion valve | Emerson | ||||
FDF | Emerson | ||||
Oil separator | Emerson | ||||
Pressure protector | Emerson | ||||
Reservoir | Standard: RSP Optional: Emerson | ||||
Sight glass | Standard: SANHUA Optional: Danfoss | ||||
Refrigeration ball valve | Standard: SANHUA Optional: Danfoss | ||||
Electric | Schneider AC contactor, Schneider intermediate relay | ||||
Refrigerant | R404A R508B R14 R50 mixed refrigerant | ||||
Safety protection |
High pressure protect;Water-supply cut-off protection;Over-current protection;Leakage protection; Sequential and phase failure protection;High temperature protection;sensor failure protection; liquid low level protection etc.multi-safety protection. |
||||
Piping material | Copper pipe | ||||
Case material | SUS 304 | ||||
Water-cooled type W (cooling water at 20℃) |
3m³/h | 4m³/h | 6m³/h | 10m³/h | |
Power | 380V 50HZ 12kw | 380V 50HZ 16kw | 380V 50HZ 24kw | 380V 50HZ 36kw | |
Connection | 750*750*1750 | 750*750*1750 | 1000*950*20500 | 1200*1100*2050 | |
Weight | 350kg | 400kg | 600kg | 950kg | |
db | within 75db | within 80db |
سوف نتصل بك في غضون 24 ساعة.